H 7201

H 7201: Feed Line and Distribution Fuse Board

? for SELV and PELV (24 V or 48 V power supply systems) ? L1/L2 rail current rating max. 92 A

? max. 63 A current rating for each individual feed terminal

? for safeguarding up to 6 individual circuits with circuit breakers ? the circuit breakers are not included within the scope of delivery.

Circuit breaker monitoring

Diagnostic Signals from Circuit breakers Suitable for digital Inputs *) Contact 2 not used

Figure 1: Circuit Diagram

Explanations

(1) C ircuit breaker with monitoring contact. (2) C ircuit breaker monitoring is operational (XG12) if the sliding switches

(SF1 to SF6) are set to the used position on the circuit breaker slots in use:

used position equipped with circuit breaker unused position not equipped with circuit breaker

(3) By inserting the provided jumper into the XG2 terminal, the two separated power rails are con-nected with one another.

Design:

For mounting on an NS 35 mounting rail in accordance with EN 60715. Printed circuit board with sockets for 2 circuit breakers of up to 60A and 4 circuit breakers of up to 16A

Width 208 mm (total width) Height 108 mm (total height) Installation depth 132 mm (equipped with circuit breakers) Protection class IP 20 Weight 0.80 kg (without circuit breakers) Temperature range 0 to 60 °C

HI 800 357 Rev. 0.08

2/3

Preferred Type of Circuit Breaker (not included within the scope of delivery of the H 7201):

Fuse

Nominal current

Make Type

HIMA no. F1, F2, F5, F6 4 A E-T-A ? 2210-S211-P1T2-H111 4 A 57 0350040 F1, F2, F5, F6 16 A E-T-A ? 2210-S211-P1T2-H111 16 A 57 0350160 F3, F4 30 A E-T-A ? 8345-C01A-R0T1-DB1B2B 30A

57 0304031 F3, F4

60 A

E-T-A ?

8345-C01A-R0T1-DB1B2B 60A

57 0304061

Table 1: Preferred Type of Circuit Breakers

Terminals and Wiring:

Terminal Min./max. wire cross section (mm 2) XG2: L+ feed line 0.2 / 16 flexible, 10 with wire end ferrule XG1:, XG3: L- feed line 0.2 / 16 flexible, 10 with wire end ferrule XG13: L+/L- outgoing line 0.5 / 25 flexible XG4 to XG7: L- outgoing line 0.2 / 2.5 flexible XG8 to XG11: L+ outgoing line

0.2 / 2.5 flexible

XG12: circuit breaker monitoring 0.2 / 2.5 flexible

Table 2: Terminals and Wiring

Diagnostic Signal Connector XG14:

The diagnostic signals can be used to detect the status of the outgoing lines XG8 through XG11 and XG13.

? HIGH signal -> voltage present ? LOW signal -> voltage not present

The diagnostic signals are suitable for digital inputs of type 3 (in accordance with IEC 61131-2) and can be evaluated by e.g. a PES.

Front View:

Figure 2: Front View with Circuit Breakers "F1 (6)

Mounting

We recommend mounting the H 7201 horizontally or vertically (with respect to the label lo-cated on the front) to ensure sufficient ventilation.

HI 800 357 Rev. 0.08 3/3

Warning! Unnecessary shut down!

At an ambient temperature ≥ 60°C and a nominal current rating of all circuit break-ers of the H 7201, the current rating must be reduced to ≤ 80 % of the nominal cur-rent rating.