9926 Series Branch Rated Circuit Breakers–AC Version

Circuit Breakers

T r i p p i n g T i m e

S e c o n d s

M i n u t e s 100105125150200

300

400500

1000

1500

200025003000

40005000

(%) Rated Current

Trip Curves—Hydraulic Magnetic Type

Typical time/current characteristics at 30oC

9926 Series Single Pole 9926 Series Double Pole

Sample trip characteristics - KM

125%150%200%400%600%800%1000%

minimum 15840.70.090.0070.005(sec)

maximum 30090

28

4

1.5

0.6

0.4

(sec)

Although the 9926 series uses a magnetic only trip mechanism, CSA testing indicates a trip characteristic similar to thermal magnetic trip mechanisms. No de-rating is required at elevated temperatures.

Technical Data Voltage 120/240 VAC, 50/60Hz

Current

minimum 0.5A maximum

25A Interrupting capacity 10,000A

Dielectric strength 1500V , 50/60Hz

Insulation resistance 100M M

Operating life

10000 mechanical operations

Operating temperature -40…+65°C

Wire size*

0.5-15A:14AWG min., 10AWG max.20-25A:10AWG min.Torque 20 in.-lb Approval

cULus listed according to UL489 CSA C22.2 No. 5.02, CE, VDE Accessories Part No.Bus-bar (1 pole, insulated, 1 m)67101904Bus-bar (2 pole, insulated, 1 m)67101972Bus-bar end cap, 1 pole 67101973Bus-bar end cap, 2 pole 67101974Power lug, straight 67101960Power lug, 90°67101961Lock-out handle

67101913

*Wire sizes: gauges specified are the minimum allowable as per CSA and UL standards.

The 9926 circuit breakers do not have provisions for marking tags. A possible solution is to cut the adhesive SchS2 tag rail to length (approximately 20 mm on a single pole unit so the current rating remains visible or approximately 30 mm on a two pole unit).The SchS2 accepts DEK, WS and ESG 8/17 marking tags.The part number for adhesive SchS2 is 1720600000.

Additional trip curves and amp ratings are available upon request.

T r i p p i n g T i m e

S e c o n d s

M i n u t e s

100105130150200

300

400500

1000

1500

200025003000

40005000

(%) Rated Current Trip Curve 1 applies to the following part numbers where "XX" is the current rating: Single Pole— 99262512XX Double Pole— 99262522XX